1 Function
Communicate with computer master station system through medias like GPRS/CDMA, Lan TCP/IP, Radio modem to transfer data;
Manage data abstractor terminal to collect data from meters connected.
The data concentrator can also be used as an independent data terminal directly connecting to meters to collect and transfer meter readings to the master computer system station.
2 Application
AMR (Automatic Metter Reading) component ,combine with CZL096-1C-24 or other EGATE AMR devices and computor system software,a AMR system can be established.
Egate AMR system can not only be used at electricity meter reading but also be used at water,gas,and other meters.
3 Features
High speed single chip computer design and embeded programming technology keeps the device has a high quality of steady and speed;
Large scale LCD display;
Modual design makes the device can be easiely being upgraded and configured ;
Flexible upward data channel,Meadia to master computer station can be easiely selected from ADSL,Data Modem,RS485,TCP/IP,GPRS/CDMA ,fibrec and Radio modem;
Flexible downward data channel, data concentrator can communcate with data abstracter terminal through mideas like PLC,mini radio modem RS485,mini busand so on.
Power falure time can beautomaticaly recorded and data recorded could be remained in the device for as long as 10 years in case of power shutdown.
4 Standard of design
The device is designed according to the national standards bellow:
DL/T743-2001 《电能量远方终端》
DL/T645-1997 《多功能电能表通信规约》
DL/T721-2000 《配电网自动化系统远方终端》
GB/T 13729-2002 远动终端通用技术条件
GB/T 4208-1993 外壳防护等级(IP代码)
GB 12192-1990 移动通信调频无线电话发射机测量方法
GB 12193-1990 移动通信调频无线电话接收机测量方法
YD/T 1028-1999 800MHz CDMA 数字蜂窝移动通信系统设备总技术规范:移动台部分
YD/T 1214-2002 900/1800MHz TDMA 数字蜂窝移动通信网通用分组无线业务(GPRS)设备技术规范:移动台
5 Specifications:
|
No.
|
Item
|
Data
|
|
1
|
Working voltage
|
3×220VAC/380VAC or 1×220VAC
|
|
2
|
Frequency
|
50+5Hz
|
|
3
|
Consumption
|
<10VA
|
|
4
|
Enviroment tenpreture
|
-25ºC~+55ºC
|
|
5
|
Enviroment tenpreture
|
<90%R·H
|
|
6
|
Sampling error
|
<+0.01%
|
|
7
|
Capacity
|
≤1024meters
|
|
8
|
Timing error
|
<+1s/d
|
|
9
|
Communication
|
RS4851200m
PLC 1500m
Miniradio Modem 800m
|
|
10
|
Communication repeater
|
Automatic repeating
|
|
11
|
Downward channel
|
2ways RS485
|
|
12
|
Upward channel
|
ADSL,MODEM、RS485、GPRS/CDMA、RS232
|
|
13
|
Dimension
|
315mm×241mm×100mm
|
|